Input
-
Input 115VAC 60Hz rated @ 3.5A.
-
-
-
Power supply input options:
-
a) One (1) common power input for ACM8/ACM8CB and lock power (factory installed).
-
b) Two (2) isolated power inputs - One (1) to power the ACM8/ACM8CB and one (1) for lock accessory power, (external power supply is required). (Current is determined by the power supply connected, not to exceed a maximum of 10A total).
-
-
-
Eight (8) Access Control System trigger inputs.
-
-
-
Input options:
-
-
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
-
Output
12VDC or 24VDC @ 6A supply current.
Eight (8) independently controlled outputs.
-
-
-
Output options:
-
-
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form "C" 5A rated relay outputs
c) Any combination of the above.
Eight (8) auxiliary power outputs (unswitched)
-
-
-
Output ratings:
-
-
Fuses are rated @ 3.5A.
Filtered and electronically regulated outputs (built-in power supply).
ACM8 board main fuse is rated at 10A.
-
Supervision
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery and battery presence supervision (form "C" contact).
Features
Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
Alarm output relay indicates that FACP input is triggered (form "C" contact rated @ 1A 28VDC).
Short circuit and thermal overload protection.
AC fail supervision (form "C" contact).
Battery Backup
- Built-in charger for sealed lead acid or gel type batteries.
- Whit backup battery capacity.
- Battery is not included.
- The battery can be: PL4.512 / PL712 / PL912.
- Automatic switch over to stand-by battery when AC fails.
- Zero voltage drop when unitswitches over to battery backup (AC failure condition).
- Battery fail and battery presence supervision (form "C" contact).
Temperature
- Operating: 0ºC to 49ºC (32ºF to 120ºF).
- Storage: - 20ºC to 70ºC ( - 4ºF to 158ºF).